6. Setpoints
6.1 Basic Settings
CT Ratio
[ /5A]
Genset phases current transformers ratio.
Step: 1 A
Range: 1 – 5000 A / 5A
Controller Mode
[OFF, MAN, AUT]
Equivalent to Controller mode changes by MODE→ or ←MODE buttons
6.2 Engine Protections
Horn Timeout
[s]
Max time limit of horn sounding. Set to zero if you want to leave the output HORN open. Horn timeout
starts again from the beginning if a new alarm appears before previous Horn timeout has elapsed.
Step: 1s
Range: 0 – 600 s
Wrn Maintenance
[h]
Counts down when the engine is running. If it reaches zero, an alarm appears. When the value 10000 is
set, the Maintanance function is disabled and counter does not count. Counter value disappears in
controllers statistics. Maximum value for running countdown is 9999.
Step: 1h
Range: 0 – 10000 h
6.3 Extension I/O (Optional equipment)
IOM AI1/2/3/4 Wrn [ ]
The warning level for IOM ANALOG INPUT 1 to 4 alarm
detection.
Step: 1
Range: -100 - +10000
IOM AI1/2/3/4 Sd [ ]
The shutdown level for IOM ANALOG INPUT 1 to 4 alarm detection.
Step: 1
Range: -100 - +10000
Содержание 10 GSC
Страница 2: ...1 Rev 3...
Страница 57: ...U_ 3002_EN Rev 2...
Страница 58: ...1 Rev 2...
Страница 71: ...14 4 1 5 History log...
Страница 99: ...42...
Страница 100: ...43 Rev 2 U_ 3002_EN Rev 2...
Страница 101: ...7 2 Genset Dimensions...
Страница 104: ......
Страница 105: ...7 3 Alternator s Connections...
Страница 106: ......
Страница 107: ......
Страница 108: ...7 4 Regulator s Connections...
Страница 109: ......
Страница 110: ......
Страница 111: ...7 5 Electrical Wiring Drawings...
Страница 116: ...7 6 Tightening Torques...
Страница 118: ...7 7 Instructions for decommissioning scrapping and disposal...