7
MINIMUM CLEARANCES
Due to the high temperature of the heater, it should be
located out of traffic and away from furniture and
draperies.
Minimum Clearances
K
Sidewall to Insert
4-1/2"
I
Side Facing
4-1/2"
M
Top Facing
35" *
N
Mantel
35" *
F
To combustible Floor
1"
X
Extension onto Hearth
1"
* Measured from the base of the insert.
Mantel Clearances
The maximum mantel depth is 12”.
NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it
does, it is considered a mantel and must meet the mantel requirements listed in this manual.
INSTALLATION REQUIREMENTS
Factory-Built (Metal) Wood-Burning Fireplace Requirements
NOTE
:
Any parts that are removed must be removed in a way that would allow them to be re-installed if
the insert is ever removed (removal of rivets or screws is acceptable).
The damper ("A") and grate (with log set) ("B") must be removed (see the illustration below)
The smoke shelf ("C"), internal baffles ("D"), screen ("E"), masonry lining or refractory ("G" & "I"), and
metal or glass doors ("F") may be removed if
they are attached by mechanical fasteners (if ap-
plicable).
The fireplace must be permanently marked to
indicate that it has been altered and is no longer
suitable for burning solid fuel (wood), unless the
removed parts are re-installed.
Cutting of any sheet metal parts is prohibited.
The insulation ("H"), and any structured rigid
frame members must not be removed or altered
(side and top of door frame, side and top of the
face of the fireplace, metal sides, etc.).
Attach the "This fireplace has been altered"
tag to the fireplace (use two screws or other
suitable method). You may wish to place it in a
location where it will be covered by the sur-
round panel.