58
7.3
Individual country settings
NOTE
MaxTalk 2 Pro can be used by authorized and trained personnel to individually adjust
the operating parameters. MaxTalk 2 Pro: professional version of MaxTalk for the con-
figuration of inverters. The required "SolarMax TS-SV series parameter configuration
using MaxTalk 2 Pro" operating manual can be downloaded from our website at
www.
solarmax.com
("Downloads" area).
7.3.1 SM330TS-SV
Parameter
Unit
Germany
Spain
Italy
France
Great Britain
Vac min 1
V
224
238
84
224
246.4
t Vac min 1
ms
2000
200
2000
200
2500
Vac max 1
V
322
308
364
336
305.2
t Vac max 1
ms
100
200
200
200
1000
Vac min 2
V
126
-
-
-
226.8
t Vac min 2
ms
1500
0
0
0
500
Vac max 2
V
-
-
-
-
313.6
t Vac max 2
ms
0
0
0
0
500
Vac 10min max
V
-
-
-
-
-
f min 1
Hz
47.5
48
45.5
47
47.5
t f min 1
ms
100
200
200
200
20000
f max 1
Hz
51.5
51
54.5
52
51.5
t f max 1
ms
100
200
200
200
90000
f min 2
Hz
-
-
-
-
47
t f min 2
ms
0
0
0
0
500
f max 2
Hz
-
-
-
-
52
t f max 2
ms
0
0
0
0
500
Restart delay
s
0
0
300
0
0
Mains check
On/Off
On
On
Off
On
On
- Vac MC max
V
364
308
308
336
305.2
- Vac MC min
V
266
238
238
224
246.4
- f MC max
Hz
50.05
51
50.1
52
51.5
- f MC min
Hz
47.5
48
49.9
47
47
- t MC monitoring
s
0
180
30
0
180
Island Detection
On/Off
Off
On
Off
Off
On
OV Detection
On/Off
On
On
On
On
On
Soft Start
W/s
-
-
-
-
-
Pac Progression
%/min
-
-
20
-
-
P(f)-Mode
(1/2/3/Off)
1
Off
3
Off
Off
- f start
Hz
50.2
50.2
50.3
50.2
50.2
- f stop
Hz
50.05
-
50.1
-
-