NOTE
■
■
The inverter is not fitted with overvoltage protection on the AC side.
■
■
The inverter does not have any devices (such as RCDs) for the protection against
dangerous touch currents or electric shock.
■
■
The inverter is fitted with a configurable DC insulation monitor (Vsym monitor, see
TS-SV operating manual).
Procedure
DANGER
Make sure that all the DC and AC feed lines to the inverter are dead before you start
the installation work.
1. Run the AC feed lines from below into the inverter and to the M8 threaded bolt connec-
tions below the AC power switches.
2. Connect the AC feed lines correctly.
– Remember that the rotating field of the mains phases must be clockwise.
– The correct order of the fastening elements is: Cable lug, spring lock washer, finally
the M8 nut.
– Tightening torque for the M8 nuts: minimum 20 Nm, maximum 25 Nm.
3. Position the included phase separation elements between the cable lugs to ensure the
isolation clearance.
4. Implement the cable strain relief within the false floor of the station (in the inverter no
cable strain relief is designed). The distance between DC connection within the in-
verter and the cable strain relief should be smaller than 500 mm.