3. Record the address set in front on the power unit.
4. Reconnect the configuration plugs.
5. Record the inverter number outside on the type plate.
Configuration plug
5.3.6 Connecting the shutdown contact 1 (optional)
Position of the shutdown contact 1 (SD1-SD4) in the inverter: see 5.3.1 “Interior view”.
The shutdown contacts 1 (SD1-SD4) enable remote shutdown of as many as eight
inverters using an external break contact (e.g. an emergency off switch). If the shutdown
function 1 is activated the current supply circuit of the AC contactor K1 is disconnected
directly and the inverter is locked. This results in the immediate disconnection from the
grid which is also effective when the control unit fails. The inverters remain locked until
the external break contact is reclosed. In addition, the status message “Shutdown 1” is
displayed.
The shutdown 1 is inactive if there is a short circuit between either the contact pair SD1
and SD2 (SD12) or SD3 and SD4 (SD34), e.g., with a plaited bridge. The shutdown 1 is
only active if both contact pairs SD12 and SD34 are open. When shipped from the factory
the contact pair SD12 is short-circuited with a plaited bridge.