21
en
8
PV1, PV2, PV4, PV5, PV7, PV8, PV10 and PV11
All types
9
PV1, PV2, PV3, PV4, PV5, PV7, PV8, PV10 and PV11
All types
10
PV1, PV2, PV3, PV4, PV5, PV6, PV7, PV8, PV10 and PV11
All types
11
PV1, PV2, PV3, PV4, PV5, PV6, PV7, PV8, PV9, PV10 and PV11
Only for SHT60
12
PV1, PV2, PV3, PV4, PV5, PV6, PV7, PV8, PV9, PV10, PV11 and PV12 Only for SHT60
Connectors of PV string cabels
Ensure that cables of the proper type are being used to connect the inverter to the PV gener-
ator. In particular, PVC and H07RN-F non-tinned cables are NOT recommended.
The PV cables must be terminated with the Amphenol H4 (MC4 compatible) provided with
the inverter.
If different types of connectors are used, or if different installation tools and procedures are
used, then it may not be possible to ensure safety and technical performance.
The following Connectors are recommended for PV strings:
■
Positive pole connector (+), female: Amphenol H4CFC4 S
PC
Insulation layer
Locking nut
Fig. 15: Positive pole emale connector
Insulation layer
Locking nut
Fig. 16: Negative pole male connector
DANGER!
Fatal electric shock hazard!
In daylight the PV generator supplies the inverter with a dangerously high DC
voltage.
■
The PV generator voltages are very high. NEVER plug or unplug the DC
connectors when the inverter is turned on, otherwise dangerous electric
arcs could develop.