Fig. 10: Securing the PE cable
NOTE
The PE wire must be well grounded to ensure that impedance between Neutral and
Earth wire be less than 10 Ω.
Connection of AC Output Cable
In the lower part of the front of the inverter there is an covered AC wiring area.
1. Remove the screws and the cover of the covered AC wiring area:
AC wiring area
Fig. 11: Removing the cover of the AC wiring area
2. Remove an appropriate length of the jacket and insulation layer from the AC output cable.
3. Insert the exposed core wires into the crimp area of the OT terminal, wrap the wire crimp
area with heat shrink tubing or insulation tape and crimp them using hydraulic pliers.