![SolarEdge StorEdge SE7600A-US1 Скачать руководство пользователя страница 75](http://html1.mh-extra.com/html/solaredge/storedge-se7600a-us1/storedge-se7600a-us1_installation-manual_1313757075.webp)
Communication Options
The following types of communication can be used to transfer the monitored information from the
inverter to the SolarEdge monitoring platform.
Only communication products offered by SolarEdge are supported.
Always connect the communication options when the relevant devices are powered down - CCG,
inverter .
Ethernet
Ethernet is used for a LAN connection. For connection instructions refer to
RS485
RS485 is used for the connection of multiple SolarEdge devices on the same bus in a master-slave
configuration. RS485 can also be used as an interface to external devices, such as meters and third party
data loggers.
l
RS485-1: Enables the connection of multiple devices (inverters/CCG) over the same bus, such that
connecting only one device to the Internet is sufficient to provide communication services for all
the devices on the bus.
l
RS485-2: Enables connection of non-SolarEdge devices.
l
RS485-E: The RS485 Expansion Kit provides an additional RS485 port for the
inverter for enhanced communications. The kit contains a module, which is
installed on the communication board, and has a 3-pin RS485 terminal block.
This Kit is provided with an installation guide, which should be reviewed prior to
connection see,
https://www.solaredge.com/sites/default/files/RS485_
expansion_kit_installation_guide.pdf
For connection instructions refer to
Creating an RS485 Bus Connection
ZigBee
This option enables wireless connection of one or several devices to a ZigBee gateway,
for wireless communication to the SolarEdge monitoring server.
The ZigBee kit is provided with an installation guide, which should be reviewed prior to
connection. Refer to
https://www.solaredge.com/sites/default/files/se-zigbee-home-
gateway-installation-guide.pdf
GSM
This wireless communication option (purchased separately) enables using a GSM
connection to connect one or several devices (depending on the data plan used) to the
SolarEdge monitoring platform.
The GSM cellular modem is provided with a user manual, which should be reviewed
prior to connection. Refer to
https://www.solaredge.com/sites/default/files/cellular_
CDMA
This wireless communication option enables using a cellular CDMA connection for connecting to the
SolarEdge monitoring platform.
Chapter 9: Setting Up Communication to the Monitoring Platform
SolarEdge
-
StorEdge Installation Guide MAN-01-00262-1.3
73
Содержание StorEdge SE7600A-US1
Страница 1: ...SolarEdge StorEdge Solution with Backup Installation Guide For North America Version 1 3 ...
Страница 116: ......