Technical Specifications
SolarEdge Installation Guide – MAN-01-00002-1.6
111
Default Trip Limits and Times according to IEEE 1547:
Voltage Range (% of Base Voltage)
Max. Clearing Time (Sec)
V < 50%
0.16
50 % < V < 88%
2.00
100% < V < 120
1.00
V > 120 %
0.16
Frequency Range (Hz)
Max. Clearing Time (Sec)
> 60.5
0.16
< 59.3
0.16
OP250-LV, OP300-MV and OP400-MV
OP250-LV
OP300-MV/
OP400-MV
Input
Rated Input DC Power
250
300/400
W
Absolute Maximum Input Voltage
55
75
Vdc
MPPT Operating Range
5 - 55
5 - 75
Vdc
Maximum Input Current
10
Adc
Reverse-Polarity Protection
Yes
Maximum Efficiency
99.5
%
European Weighted Efficiency
98.8
%
CEC Weighted Efficiency
98.7
%
Nighttime Power Consumption
< 2.5
W
Overvoltage Category
II