UPS for 400 Vac Grid, Installation Guide, doc. rel. 3.0
5
If you remove a power module from the UPS while the module is operating, wait five minutes
before reinserting the module. This allows the module’s capacitors time to discharge.
FAST FUSES (SEMICONDUCTOR FUSES) must be used between the battery and the UPS
–
for
example, the Ferraz Shawmut A70QS fuse.
WARNING - RISK OF LETHAL ELECTRIC SHOCK:
WARNING! HIGH TOUCH CURRENT!
EARTH CONNECTION ESSENTIAL BEFORE CONNECTING SUPPLY.
WARNING - RISK OF LETHAL ELECTRIC SHOCK:
The battery cabinet contains a series of batteries that provides high
voltage and energy in the UPS body even when the UPS is not
connected to the ac input.
Take appropriate precautions during installation, inspection and
servicing.
Don’ts
Do not open the cover of the UPS or the battery cabinets under any circumstances. All UPS
panels and doors should be closed.
Do not insert any objects through the ventilation holes.
Do not put objects on the UPS.
Do not move the UPS while it is operating.
Do not use the UPS outdoors.
Do not turn the UPS upside down or lying down during transportation.
Do not connect or disconnect any AC or DC cables to the battery cabinet or UPS unless ALL
the battery circuit and AC circuit breakers are turned OFF.
Do not turn ON the battery circuit breaker when the battery cabinet is disconnected from the
UPS.
Do not install the UPS next to gas or electrical heaters. A restricted location is recommended
in order to prevent access by unauthorized personnel.