UPS for 400 Vac Grid, Installation Guide, doc. rel. 3.0
75
To avoid such a hazard in decentralized mode, the static switches are synchronized by dedicated
control communication to ensure that if one unit goes to Bypass mode, the rest of the units will
also transfer to Bypass mode simultaneously.
6.1.2.
Parallel communication
When two or more UPS units are operated in parallel, parallel communication must take place
between them in a "ring" arrangement. This is accomplished by the use of Gamatronic-provided
cables with D25 connectors on each end. Parallel communication keeps the parallel units
synchronized with each other and is used to pass commands and status information between
units.
Each UPS has two D25 parallel communication connection terminals.
Figure 53 below shows how to connect the parallel communication terminals for parallel
operation of two and three UPS units. When connecting one UPS to the other, it does not matter
which of the two D25 terminals you use on each UPS.
Figure 53: Parallel comm. connections (see Table 9)