DRAGON POWER 1-L

1 KVA - 3 KVA

USER MANUAL

Содержание DRAGON POWER 1-L

Страница 1: ...DRAGON POWER 1 L 1 KVA 3 KVA USER MANUAL...

Страница 2: ...atches ringsor similar metal objects B Use insulatedtools C Wear rubbershoesandgloves D Donot place metal tools or similarparts on the battery E Disconnectthe load fromthe batteries before removingthe...

Страница 3: ...play 6 3 2Functionof button 7 3 3UPS workingstatustable of LCDdisplay 8 3 4Parameter query 9 3 5Functionsetting 10 4 Warningcode faultcodeandsolution 13 4 1Warningcodeandsolution 13 4 2Fault codeandso...

Страница 4: ...s It continuously adjusts and filters the input voltage When the power supply is interrupted itwill providethe backuppowerfromthe backupbattery without timeinterruption In case of overload or inverter...

Страница 5: ...uterinterface Smart slot optional Externalbattery connection USB Input over currentprotection ACINPUT Outputsocket EPO Battery interface Battery breaker optional Maintenance bypassswitch optional Outp...

Страница 6: ...e sine wave Overload time Linemode 10min 102 110 load 1min 110 130 load 10s 130 150 load Battery mode 1min 102 110 load 10s 110 130 load 30s 130 150 load Efficiency Line Mode 94 Battery Mode 93 ECOMod...

Страница 7: ...nly inanambient temperature range of0 40 32 104 Install it in a clean environment free from moisture flammableliquids gasesand corrosivesubstance ThisUPS containsnouser serviceablepartsexcepttheintern...

Страница 8: ...statusmonitoring connectthe communicationcable one end to the USB RS232port and the other to the communicationport of your PC With the monitoring software installed you can schedule UPS shutdown start...

Страница 9: ...ation Thebattery capacity 0 25 26 50 51 75 76 100 isdisplayed separately andthe battery iconflasheswhen the battery is low or not connected Other information AC Battery Bypass Inverter Outputworking F...

Страница 10: ...eckingand mute function Testing in ACMode pressthe two buttons at the same time for 2secondsabove to test the battery Mute in Battery Mode Alarm TestingMode presstwo buttons at the sametime for 2 seco...

Страница 11: ...on When the ACinput isout of limited rangeor shutoff the UPS will turn to Battery Mode Thebatteries supplythe inverter and have beepevery 4seconds BypassMode LCDdisplaycontent Instruction When theACin...

Страница 12: ...larm information by default When UPS keepsnormal working the homepagedefault display will show the output voltage and frequency information Press right button more than 2sec LCDwill turn to the pollin...

Страница 13: ...onfirmation button 0 5 2sec thenfinish the OPUsetting Thenumberbyleft sideofOPUwill keeplightingon no flashing 4 Press functional setting button over 2 sec quit the settingpageandbacktothe homepage Or...

Страница 14: ...load 50 02 3 EconomicOperation Mode LCDDisplay Setting ECOisOFF bydefault canbe set as ONto improve the efficiency ofsystemoperation Note For the modelswith PF 1 OFFbydefault andunableto set 02 4 Eme...

Страница 15: ...argerCurrent CHG LCDDisplay Setting When EP is set to ON the CHGoption appearson the functional settingpage the chargingcurrent canbeset 1 12Aoptional default 1A Noted if UPS built inbatteries the cha...

Страница 16: ...utral andthe live cables 2 Checkthe groundcable connection 8 Battery over voltage UPS detects highbattery voltage Checkthat the battery quantity setting isconsistentwith the actual battery quantity 9...

Страница 17: ...nel of the UPS is blocked 3 Overload 4 NTCsensorabnormality or abnormalwiring 5 Power componentIGBT is damaged 1 Please checkthe rectifier fan 2 Clean the obstacles onthe air ductof the rear panelof t...

Страница 18: ...fthe voltagehasbeen reduced 67 Chargingover voltageor battery connection reversed 1 Hardware error 2 Number of battery wrong 3 Wiring wrong 1 Checkwhether the battery wiring or battery number meetsthe...

Страница 19: ...oad Remove all loadsand restart the machine 5 With city electricity butno city electricity indication Mains voltage or frequencyover UPS inputrange Useamulti metertocheck whether the input voltageand...

Страница 20: ...9 PhoenixDescription UPS fault 1 9 Openfromcommonconnection UPS isabnormal Closed UPS is normal General 2 7 Openfromcommonconnection UPS iswarning Closed UPS is normal GND 3 2 Internal GND usedtoconne...

Страница 21: ...4 5 9 8 7 Battery low UPS is on Utility fail UPS fail General alarm Remote shutdown GND VCC 5 3EPO Theremote EPO islocated onthe rear panel of UPS Its normal closed if its open it will active EPO func...

Страница 22: ...time shouldnotbeless than12hours In normalcircumstances service life of the battery is 3 5years if the battery isfoundto be in poor condition it must bereplaced in advance When replacingthe battery it...

Страница 23: ...www lbspower com Espa ol English...