System Setup and Operation Manual for ATSC MS3 L0
Operation and Setup Menu
To Battery Charge Parameter Setup Menus
Set for total amp hours of all connected battery(s). (The
value must be greater than or equal to the total capacity
of the system when there is a PRO-Verter)
Set charge efficiency mode to AUTO ADJUST—it
automatically adjusts based on actual charge efficiency
to continuously improve remaining battery capacity
accuracy.
Self-discharge rate set at 3% per month at 25 °C (lithium
and AGM battery)
Maximum charge voltage set-point limit regardless of
other settings or temperature compensation
Set to 29.0 V
Note: All AUX functions disabled in this system
configuration
Sets charge controller Load Control mode
to be based on battery volts or battery amp hours. Setting
units (V or Ah) in setting screens change based on present
mode setting.
Note:
Be certain to set voltage settings even if using
amp hour control, as the charge controller will default to
voltage control if battery amp hours are unavailable.
Enables, disables, and sets ON time for Lighting Control
mode. Lighting Control mode is disabled if BOTH post-
dusk and pre-dawn timers are set to DISABLED (< 0.5 hrs).
Lighting Control mode is enabled if either post-dusk or pre-
dawn timers are set to time value.
Note: All auto lighting
disabled in this system configuration
Corrects for “zero offset” in net battery current display.
Caution:
Be certain shunt signal is a true zero before
performing this function or inaccurate battery current and
amp hour readings will result.
Restores all factory default settings in the charge control
system.
Sets display backlight to ON, OFF, AUTO. In AUTO,
backlight remains ON for one minute following the last key
press.
SET BAT AMP-HRS
450 AH
SEL
SET CHG EFFENCY
94% SEL
SET SELF-DISCHG
3%/MONTH SEL
SET MAXIMUM BAT
VOLTS 29.0V SEL
SET AUX OUT MODE
BAT VOLTS
SEL
SET AUX OUT OFF
<23.0
SEL
SET AUX OUT OFF
<25.2
SEL
POST-DUSK LIGHTS
ON 2.5 HRS SEL
PRE-DAWN LIGHTS
DISABLED
SEL
SET BACK-LIGHT
AUTO
SEL
RESET CURRENT
SHUNT ZERO SEL
RESET DEFAULT
SETTINGS
SEL
SET BAT CHARGE
PARAMETERS SEL
SET CHGEFFENCY MDE
AUTO ADJ
SEL
Provides operational setup and auxiliary functions