background image

Operation & Installation Manual

HEAT PUMP

Содержание ATMOS AIR 270

Страница 1: ...Operation Installation Manual HEAT PUMP ...

Страница 2: ...ct Please take the time to read it through before operating Once the installation is complete check that all connections are secure before the power is turned on The installer is to explain to the end user how to operate and maintain the unit in accordance to this instruction manual If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified perso...

Страница 3: ...connection 12 4 5 trial running 12 5 Usage 13 5 1 function of wire controller 13 5 2 usage of wire controller 15 6 Maintenance and repair 24 7 Appendix 30 6 2 trouble shooting guide 6 3 major service 6 4 water supplies water chemistry and water quality 6 5 product warranty 25 26 26 28 6 1 maintenance 24 4 6 seismic restraints 12 30 31 7 1 caution 31 7 2 the method of grounding 32 7 3 use of the P ...

Страница 4: ...ing Compulsory The listed action must be implemented Attention to what is indicated Prohibited Next to this icon The heat pump must be installed by qualified personnel Improper installation could result in electrical shock water leakage or fire Please ensure that the unit and power connections have a good earth Fail to do this may cause an electrical shock Professional installer required Earthing ...

Страница 5: ...rtant If the heat pump needs to be relocated or installed again only use an authorised dealer or qualified personnel It is prohibited for the end user to repair the unit themselves unless qualified Fail to do so may lead to serious injury or and damage to the unit Should the heat pump need to be repaired only use an authorised dealer or qualified personnel Prohibited Important OPERATION ATTENTION ...

Страница 6: ...hich are unsuitable for solar hot water heating 2 2 Characteristics Easy to operate Featuring an easy to use timer for both start and stop operations with a controller to set the desired water temperature Safe and environmentally friendly Produces no harmful gases along with no open flame making the unit safe to work with when installing Air inlet Air outlet Controller Tank ...

Страница 7: ...surized vapor is cooled down through the heat exchanger with the water in the tank until it condenses into a high pressure moderate temperature liquid Then the pressure of the liqiud refrigerant drops as it passes throttling device Finally refrigerant absorbs heat from the surrounding air and evaporates into vapor with low temperature and low pressure and then it goes into compressor again The coo...

Страница 8: ... MODEL ATMOS AIR 270 Φ640 16 5 B A C P T valve Over heating protector Electric heater Drainpipe 98 5 D E Cold water inlet Hot water outlet Condensation water outlet Magnesium Model A mm B mm C mm D mm E mm ATMOS AIR 270 1955 1425 577 1195 1095 ...

Страница 9: ... of the units See package label See nameplate 2 Specifications 2 5 performance parameters 6 Work range 1 Ambient temperature is 5 43 Heat Pump Measurement conditions Instant heating Ambient temperature20 15 Water inlet 15 Water outlet 55 Operating parameters The range of the operating water pressures 0 15 0 7MPa FREEZE PROTECTION The water heater has a freeze protection system The freeze protectio...

Страница 10: ...t will defrost automatically maximizing the heating efficiency Lasting 2 10 minutes The fan motor will stop running whilst the unit is defrosting Water pressure protection temperature or When the tank pressure reaches 0 85MPa or when the tank temperature reach 99 the P T valve will open automatically so as to release the pressure or decrease the temperature 7 In order to use the unit correctly ple...

Страница 11: ...sure that the flexible drainpipe is pointing downwards and exposed in the air Water Inlet Y shaped Filter Tap Water Thermal expansion tank if required Barrel drain Drainpipe Condensate Outlet P T Valve Water Outlet Notice Tempering valve required Magnesium ATTENTION The P T valve attached with the unit must be installed fail to do so Setup cannot affect the building structure and safety Notice A p...

Страница 12: ...ination angle of 60 degree is not exceeded If transport in an inclined position cannot be avoided the unit should be placed into operation one hour after it has been moved into final position Transportation CAUTION High center of gravity WARNING For continued safety of this appliance it must be installed operated and maintained in accordance with the manufacturer s instructions If the water supply...

Страница 13: ...Air inlet 4 Installation 4 3 Installation space Before installation please ensure that you leave the space as shown below for maintenance Air outlet Display Barrier 500 1000 300 Unit mm 10 600 500 ...

Страница 14: ...tallation House eave Rain The is designed for external installation however if possible installing the system under the house eave or in a sheltered environment may help prolong the life of the system Heat pump ...

Страница 15: ...ck that all power connections are secure before switching on 4 5 2 Trial running Switch on the unit using the controller In the case of any unusual noise switch the power off and consult your provider If the power cord is damaged It must be replaced by a qualified electrician The parameters have been pre set to a temperature of 60 degrees 4 6 Seismic restraints The unit must be braced with with se...

Страница 16: ...6 ON OFF Mode Electric Heater Up Down Turn on off the unit Switch unit running modes or save setting parameters Set the clock or the timer Turn on off the electric heater or switch fan modes Move up or increase parameter values Move down or decrease parameter values Clock Main display area Auxiliary display area 1 2 3 4 5 6 ...

Страница 17: ...minute Second Shows that the main display area displays the second Centigrade Shows that the temperature in Main display area or Auxiliary display area is in Fahrenheit Shows that the temperature in Main display area or Auxiliary display area is in Parameter setting Shows that the parameter is adjustable Lock Shows that the keyboard is locked Status icon What it means Heating Vacation Shows that t...

Страница 18: ...ple Intelligent Running interface 5 2 1 Turn ON OFF the unit Press and hold for 0 5s in the standby interface of the wire controller to turn on the unit and at this time the main display area shows the water outlet temperature Press and hold for 0 5s in the running interface of the wire controller to turn off the unit and at this time the main display area shows OFF Note The ON OFF button can only...

Страница 19: ...5s the controller exits the parameter modification menu by timeout and the changes are confirmed Setting 75 C When the target temperature is adjusted to 60 C press and hold the for 5s At this time the target temperature is displayed as 61 C and the temperature range changed to 38 75 C Press the to set the target temperature to 75 C Example Change the target temperature from 55 C to 70 C when the a...

Страница 20: ...our parameter will flash then press or to change it After making the changes to the parameter press to confirm then change the minute parameter as well as the date parameter in the same way If no operations are performed on the keypad for 10s the controller exits the parameter modification menu by timeout and the changes are confirmed Note Set the date in the same way when in vacation mode Example...

Страница 21: ...the timer1 setting you can set the turn on time of timer2 After finishing the OFF and 2 will flash and then you can set the turn off time of timer2 Press again to save and back to the interface If you don t need to set the timer2 you can press the to save after finishing the timer1 setting You will find the ON and 2 flash No operation for 5s the program will back to the interface automatically Not...

Страница 22: ...into the next setting without confirm the previous one ON 2 Press and hold for 2s to enter into the next setting without confirm the previous one Press and hold for 2s to enter into the next setting without confirm the previous one Press to confirm the time Press to cancel the setting Set the hour Set the minute OFF 2 ...

Страница 23: ...0 20 00 Outlet water temperature Current time Press and hold for 2s ON 1 OFF 1 Press to confirm Successful setting Press to cancel the setting and exit Without saving Confirm the time after setting Confirm the time after setting ON 2 OFF 2 Confirm the time after setting ...

Страница 24: ... flashing at this time Then set the date in the same way as 2 4 Example Set the start up date on September 28 Note Turn off the unit before going out Vacation mode Outlet water temperature The current date ON Press and hold for 0 5s Press then to set the date to September Press then Press to save Press to cancel Month day Press and hold for 2s ...

Страница 25: ... Usage 22 5 2 5 3 If you want to cancel the timer setting follow this below press to cancel all the operation Outlet water temperature Timer state Pressing lasting for 2S The ON and 1 icons are flashing ...

Страница 26: ...e unit is heating or standby Press once to turn on the electric heater and press again to shut it off Electric heater Electric heater 5 2 7 Keyboard locking Press and hold for 5s once to lock the keyboard Press and hold for 5s again to unlock the keyboard Press and hold for 5s Lock icon ...

Страница 27: ...good the wiring is tight Don t power off the unit when you use it incontinually in cold weather or the water in the pipe will freeze and split the pipe 6 1 Maintenance If the power supply cord is damaged it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard Steps for replacing the magnesium rod Check the state of the magnesium rod h...

Страница 28: ...ssure is low Low pressure switch action No water or litter water in water system Wired remote control with master signal failure Ambient temperature is too low Water flow volume not enough Water system pressure difference is small Water flow volume not enough Water system pressure difference is small Check or change the water bottom temp sensor Check or change the water top tank temp sensor Check ...

Страница 29: ...e water heater every five 5 years Replace the temperature pressure relief valve Inspect and flush the expansion control valve if fitted If required replace the valve Visually check the unit for any potential problems Inspect all connections Check the condensate drain Inspect and if required replace the anode Check the electric heating unit for excessive calcium build up or corrosion and replace if...

Страница 30: ...ectrical appliances automatic washing machines and dishwashers which are connected to the hot water supply The hydrogen which is highly flammable should be vented safely by opening a hot tap and allowing the water to flow There should be no smoking or naked flame near the tap whilst it is turned on Any hydrogen gas will be dissipated This is indicated by an unusual spurting of the water from the t...

Страница 31: ...ds TDS not suitable for anode type Saturation Index SI 1 0 Saturation Index SI 0 4 Chloride 250 mg L pH 6 0 Component Water heater cylinder Water heater cylinder Water heater Water heater Water heater Water heater 6 5 Product Warranty 2 Years on cylinder 2 Years on Heat Exchanger Gas System Compressor sealed systems 1 Year on other components The decision of whether to repair or replace a faulty c...

Страница 32: ...The Solahart warranty does not cover faults that are a result of i Accidental damage to the water heater or any component for example i Acts of God such as floods storms fires lightning strikes and the like and ii third party acts or comissions ii Misuse or abnormal use of the water heater iii Installation not in accordance with the Owner s Guide and Installation Instructions or with relevant stat...

Страница 33: ...bing so that any discharge from the valve exits only within 6 inches above or at any distance below the structural floor and does not contact any live electrical part The discharge opening must not be blocked or reduced in size under any circumstances 3 Children should be supervised toensure that theydo not playwith the appliance 4 The appliance is fitted with means for disconnection from the supp...

Страница 34: ...e pulled once every six months so as to remove the calcium carbonate deposition decrease the temperature Take care as the temperature of the discharging water is very high Vent pipes should be thermally insulated to prevent the pipes freezing in the winter Remark P T valve Model PTR20 action tempreture 99 action pressure 0 85MPa WARNING Fail to operate the relief valve easing gear at least once ev...

Страница 35: ... drain outlet loosen the screws and open the cover Press the red button to reset 7 5 Use of the overheating protector DANGER The operation of the thermal cut out indicates a possibly dangerous situation Do not reset the thermal cut out until the water heater has been serviced by a qualified personnel The overheat protector is used to turn the power off preventing the water from being heated too hi...

Страница 36: ...NOTES ...

Страница 37: ...NOTES ...

Страница 38: ...NOTES ...

Страница 39: ...NOTES ...

Страница 40: ...t Industries Registered Office 1 Alan Street Rydalmere New South Wales 2116 Australia Telephone International Sales 61 2 9684 9100 Facsimile International Sales 61 2 9684 9180 Email solahart solahart com au Web www solahart com ...

Отзывы: