SOFAR 15~24KTLX-G3
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 61 -
Setting" interface, and then Short press DOWN button to enter the "10. Set
AntiReflux" interface, long press DOWN button to confirm the input password
(initial password is 0001), the power setting can be entered by pressing the UP or
DOWM button to find the "Reflux Enable", and Long press the DOWM button for
confirmation; Press the up or DOWM button to change the size of the value, and
then long press the DOWM button to complete the input of the current value, and
enter the setting of the next value. After setting the fourth number, long press the
DOWM button to confirm, the value selection of antiReflux power can be
completed.
Note: Explanation of professional terms:
CTR Totalpower:The Sum of three-phase selling power of the connection point <=
The set Reflux power
CTR Phasepower:The sum of the three phase power vector of the connection point
= The set Reflux power
CTR SellingPower:The selling power of any phase of the system connection point
<=The set Reflux power /3
Selling electricity: sending electricity to the grid
Buy electricity: take energy from the grid
Anti-Reflux: limit the energy sent to the grid
Positive power: the power purchased
Negative power: the power of selling electricity