SOFAR 15~24KTLX-G3
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 27 -
using a crimping tool, as shown as figure 5.3. Recommend using OT terminal:
OT-M6, Cable:
≥
4mm
2
Figure 5-3 Grounding connection instruction
(
2
)
Note 1:
L3 is the length between the insulation layer of the ground cable and
crimped part. L4 is the distance between the crimped part and core wires
protruding from the crimped part.
Note 2:
The cavity formed after crimping the conductor crimp strip shall wrap the
core wires completely. The core wires shall contact the terminal closely.
Step 3:
Tighten the OT terminal by using M6 screw. Recommend torque is 5N.m
Figure 5-4 Inverter external grounding instruction diagram
5.3. Connect grid side of inverter (AC-Output)
SOFAR 15~24KTLX-G3 connect to utility grid by using AC power cable. The AC
connection must meet the requirement of local grid operator
1. M6 screw 2. OT terminal 3. threaded hole