![Sofar solar 15KTLX-G3 Скачать руководство пользователя страница 42](http://html.mh-extra.com/html/sofar-solar/15ktlx-g3/15ktlx-g3_user-manual_1311968042.webp)
SOFAR 15~24KTLX-G3
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 38 -
K4
K3
K2
K1
G
L4
L3
L2
L1
RRCR
Figure 5- 18 Inverter – RRCR Connection
Pin NO.
Pin name
Description
Connected to (RRCR)
9
L1
Relay contact 1 input
K1 - Relay 1 output
10
L2
Relay contact 2 input
K2 - Relay 2 output
11
L3
Relay contact 3 input
K3 - Relay 3 output
12
L4
Relay contact 4 input
K4 - Relay 4 output
7
G
GND
Relays common node
Table 5- 5 Function description of the terminal
Relay status: close is 1, open is 0
L1
L2
L3
L4
Active Power
Cos(φ)
1
0
0
0
0%
1
0
1
0
0
30%
1
0
0
1
0
60%
1
0
0
0
1
100%
1
Table 5- 6 4 port RRCR power levels
(c)
Logic interface for EN50549-1:2019, is in order to cease active power output
within five seconds following an instruction being received at the input interface.