50
EN
MASTERYS BC+ 60-80 kVA - Ref.: IOMMASBCXX0F-EN 00
11.12 KIT FOR TN-C / NEUTRAL-GROUND CONNECTION
To deal with different plant needs, a connection bar between Neutral and Protection Earth is available as an option
(see figure). For further information contact SOCOMEC.
The UPS does not ensure continuity of the neutral conductor.
The output neutral must not be used as a PEN connection for the load.
A PEN conductor is prohibited in the case of unbalanced and third harmonic current circulation.
TN-C-S connection
TN-C connection
N
N
N
Aux mains
Input mains
PEN
N
N
N
Output
Aux mains
Input mains
PEN
Use the same Neutral PEN section of the power connections.