14
EN
MASTERYS BC+ 60-80 kVA - Ref.: IOMMASBCXX0F-EN 00
4.3 ELECTRICAL REQUIREMENTS
NOTE!
Before carrying out any operations on the unit read the 'Safety standards' chapter carefully.
The installation and system must comply with national plant regulations.
The electrical distribution panel must have a sectioning and protection system installed for input and auxiliary mains.
RCD is not necessary when the UPS is installed in a TN-S system.
RCD is not allowed on TN-C systems.
If a RCD is required a B-type should be used.
Size of input protection devices
In/Out
phase
Model rating
Input Mains Breaker
(1)
Aux Mains Breaker
(1)
Differential input
Battery protection
(4)
(kVA)
(A)
A
B
Selective type
Fuse type aR
3/3
60
125
125
0.5
160
80
160
160
0.5
200
Cable core size
(2)
In/Out
phase
Model rating
Input
Auxiliary
Output
Battery
(kVA)
(mm
2
)
Max
(3)
3/3
60
50
50
50
95
50
80
50
50
50
95
50
50 mm
2
Tightening torque 5 Nm
95 mm
2
Tightening torque 8 Nm
1. Circuit breaker switch recommended with magnetic intervention threshold
®
10 In (curve C). It is necessary to use a D curve
selective breaker if an optional external transformer is used.
2.
For parallel configuration
, cables shall have the same size and length for each unit (maximum length tolerance is ±5%).
Output cables should be less than 25 metres.
3. Determined by the size of the terminals.
4. Tripole protection on external battery cabinet.
Recommended values to avoid unwanted tripping with UPS at full power, minimum battery voltage and backup time of at
least 5 min. Recommended Rapid fuse type or thermal-magnetic circuit breaker with intervention threshold = 3 In suited for
DC applications.
CAUTION: Residual Current Detection (RCD) can only be used in the case of a common input
and auxiliary mains (configuration not recommended). It has to be placed upstream of the
connection between input mains and auxiliary mains. If RCD is installed the trigger value must be
0.5 A multiplied by the number of units connected in parallel.
Use type B four-pole selective (S) residual current detectors. Load leakage currents are to be
added to those generated by the UPS and during transitory phases (power failures and power
returns) short current peaks may occur. If loads with high leakage current are present, adjust
the residual current protection. It is advisable in all cases to carry out a preliminary check on the
earth current leakage with the UPS installed and operational with the definitive load, so as to
prevent the RCD tipping over.
NOTE:
To ensure the integrity of the 60-80 kVA 3/3 bypass thyristors, I
2
t must be lower than 120 kA
2
s
and peak current must be lower than 5 kA for 10 ms.
Contact SOCOMEC for detailed information.
The UPS is designed for transient overvoltages in category II installations. If the UPS is part of
the building’s electrical circuit, or is likely to be subject to transient overvoltages in category
III installations, additional external protection must be provided, either on the UPS or in the AC
power supply network powering the UPS.
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK