MASTERYS BC+ 60-80 kVA - Ref.: IOMMASBCXX0F-EN 00
ADDITIONAL REQUIREMENTS FOR PARALLEL CONFIGURATION
The UPS is designed for transient overvoltages in category II installations. If the UPS is part of a
parallel configuration and the total output rated current is > 400 A, additional external protection
must be provided.
The phase rotation of aux mains and output cables must be the same for each unit.
System shutdown switch
H
should always be installed in the external distribution cabinet and
recognised as an emergency shutdown switch (red handle). If this switch is far from the UPS or in
another room a remote shutdown button shall be installed near the UPS.
Before turning on an individual unit ensure that the relevant unit output switch
G
is closed.
Before opening unit output switch
G
ensure that the relevant unit is turned off.
If unit output switches
G
are present, it is advisable to connect a normally open early break
contact from the switch to the unit’s parallel board.
If an external maintenance bypass switch
F
is present, it is advisable to connect a normally
closed early make contact from the switch to the parallel board of the concentrator unit.
If a system shutdown switch
H
is present, it is advisable to connect a normally closed early
break contact from the switch to the parallel board of the concentrator unit.
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK