MODULYS GP Green Power 2.0
range from 25 to 200 kVA - Ref.: IOMMODGPXX05-GB 01
ENGLISH
2.2. HANDLING
• The packaging guarantees the stability of the unit during shipping and physical transfer.
• The unit must remain in a vertical position during all shipping and handling operations.
• Ensure that the floor is strong enough to support the weight of the unit.
• Carry the packaged unit as close as possible to the installation site.
WARNING! HEAVY WEIGHT!
Move the unit using a fork lift truck taking the utmost caution at all times.
The unit MUST be handled by at least two people. The people MUST take position at the sides of the UPS with
respect to the direction of movement.
Do not move the unit by putting pressure on the front door.
When moving the unit on even slightly sloping surfaces, use the locking equipment and braking devices to ensure
that the unit does not fall over.
WARNING!
The following instructions must be carried out prior to moving the unit (after initial positioning).
Failure to heed this warning could result in the unit falling over, equipment damage, injury and even death.
WARNING! RISK OF TIPPING OVER!
The four feet must be secured evenly to ensure the unit is stable.
2.
ENVIRONMENTAL REQUIREMENTS AND HANDLING
2.2-1
A
B
C
10 mm
2.3. FLOOR
MOUNTING
Refer to 'connections' chapter.