MODULYS GP Green Power 2.0
range from 25 to 200 kVA - Ref.: IOMMODGPXX05-GB 01
6. CONTROL PANEL
6-1
LED indicator
Colour
Power module
Bypass module
Green
Module on inverter
Bypass ready to start
Flashing green
-
Load on bypass
Yellow
Module ready to start
Maintenance bypass
Flashing yellow
Module initialising
Load on inverter or bypass and transfer impossible/locked
Red
Module stopped due to alert
Bypass alert present
Flashing red
Initialising failure
Bypass blocked with alert
Flashing green yellow and red
No communication
No communication
Control panel luminous status bar indicator
Colour
Status
Green
Load protected on inverter
Flashing green
UPS in startup procedure phase or battery test
Yellow
Load supplied with warning (Bypass, maintenance bypass or battery)
Flashing yellow
Maintenance request/in progress
Flashing green and yellow
Load supplied and preventive alert present
Red
Load not supplied: output switched OFF due to an alert
Flashing red
Load supplied, but the output will stop in few minutes (imminent stop)
Flashing yellow and red
Load supplied, but no more protected
A critical alert has occurred
Flashing green yellow and red
No communication
Luminous status bar
Power module LED indicators
Power module LED indicators
Bypass module LED indicator