44
MODULYS GP Green Power 2.0
range from 25 to 200 kVA - Ref.: IOMMODGPXX05-GB 01
11. MAINTENANCE
NOTE!
Before carrying out any operations on the unit read the Safety standards chapter carefully.
NOTE!
Any work carried out on the equipment must be performed by qualified technicians authorised by SOCOMEC.
Routine maintenance carried out annually is recommended in order to provide optimum operating efficiency and avoid dequipment
downtime.
Maintenance consists of thorough functionality checks on:
- electronic and mechanical parts;
- dust removal;
- battery inspection;
- software updating;
- environmental checks.
BATTERIES
The condition of the battery is fundamental to UPS operation.
During the operating lifetime of the battery, the UPS stores statistics on the conditions of use of the battery for analysis.
The expected life time of the batteries is very much dependent on operating conditions:
- number of charging and discharging cycles;
- load rate;
- temperature.
NOTE!
Batteries must only be replaced with batteries recommended or sold by the manufacturer. Batteries must only be
replaced by qualified technicians.
BEWARE!
Used batteries contain harmful substances. Do not open the plastic cover!
NOTE!
Used batteries have to be placed in the appropriate containers to avoid leakage acid.
They should only be entrusted to a specialist waste disposal company.
FANS & CAPACITORS
The lifespan of consumable parts such as fans and capacitors (AC and DC) depends on whether or not the use and environmental
conditions (premises, usage or load type) are abnormal or harsh for the equipment.
It is advisable to replace consumables as follows
(1)
:
Consumable part
Years
Fan
5
DC capacitor
5
1. Based on operation of the unit according to the manufacturer’s specification.