ENGLISH
IOMMASGPXX01-GB_01
57
10-40 kVA
10
OPTIONS
10.8.1 Protection on Mains Supply and on Auxiliary Mains Supply.
Activating UPS protection on the mimic panel: access the
Configuration
menu on the mimic panel (see the
Con-
figuration
Menu section in the manual) and set the
BACKFEED TYPE
parameter to
2.BYPASS-INPUT Alone
.
Diagram of principle.
Legend.
A
Distribution panel
B
Coil remote switch
L1-L2-L3-N
Input power source
L11-L21-L31-N1
Backup power source
M1
Input power terminal board
M2
Backup power terminal board
T1
Remote
switch
1
T2
Remote
switch
1
Q1
Input power switch
Q2
Backup power switch
XB1
Connector on BKF PCB
XB2
Connector on BKF PCB
10.8.1-1
A
UPS
L11
Q2
L21
L
3
1
N1
T2
B
M2
L11
L21
L
3
1
N1
XB1
XB2
BK
F
card
L1
Q1
L2
L
3
N
T1
B
M1
L1
L2
L
3
N
UPS 3/3 with separate auxiliary supply.
10.8.1-2
A
UPS
Q2
L11
N1
T2
B
M2
L11
N1
XB1
XB2
BK
F
card
L1
Q1
L2
L
3
N
T1
B
M1
L1
L2
L
3
N
UPS 3/1 with separate auxiliary supply.
1
Remote switches - rated current
Model
T1
T2
10 3/1
32 A AC1
45 A AC1
15 3/1
32 A AC1
45 A AC1
20 3/1
45 A AC1
60 A AC1
10 3/3
32 A AC1
32 A AC1
15 3/3
32 A AC1
32 A AC1
20 3/3
45 A AC1
45 A AC1
30 3/3
60 A AC1
60 A AC1
40 3/3
90 A AC1
90 A AC1
Содержание Masterys Green Power
Страница 1: ...INSTALLATION AND OPERATING MANUAL IOMMASGPXX01 GB_01 10 40 kVA...
Страница 2: ...ITALIANO...
Страница 62: ......