54
EN
DIRIS B-10L - 551174A - SOCOMEC
Load curves – Load 1
The following Modbus table can be used only if one of the following profiles is selected:
•
Profile 6 (Single-load Load curves)
•
Profile 7 (Multi-load Load curves)
Dec address Hex address
Words
count
Description
Unit
Data type
Function
Profil
16384
0x4000
1
Load status
0: Disabled
1: Enabled
-
U16
READ
6/7
16385
0x4001
2
Date (last point)
s
DATETIME
READ
6/7
16387
0x4003
2
Total Positive Active Power - last point
W
U32
READ
6/7
16389
0x4005
2
Total Negative Active Power - last point
W
U32
READ
6
16391
0x4007
2
Total Positive Reactive Power - last point
var
U32
READ
6
16393
0x4009
2
Total Negative Reactive Power - last point
var
U32
READ
6
16395
0x400B
1
Flag - last point
0 : Complete period - date configured
1 : Incomplete period - date not configured
2 : Complete period - date configured
3 : Incomplete period - date not configured
-
U16
READ
6/7
16396
0x400C
2
Date (previous point)
s
DATETIME
READ
6/7
16398
0x400E
2
Total Positive Active Power - previous point
W
U32
READ
6/7
16400
0x4010
2
Total Negative Active Power - previous point
W
U32
READ
6
16402
0x4012
2
Total Positive Reactive Power - previous point
var
U32
READ
6
16404
0x4014
2
Total Negative Reactive Power - previous point
var
U32
READ
6
16406
0x4016
1
Flag - previous point
0 : Complete period - date configured
1 : Incomplete period - date not configured
2 : Complete period - date configured
3 : Incomplete period - date not configured
-
U16
READ
6/7