53
EN
DIRIS B-10L - 551174A - SOCOMEC
Temperature probes 1, 2, 3
The following Modbus table can be used only if one of the following profiles is selected:
•
Profile 4 (Single-load Monitoring)
Probe 1:
Dec address
Hex address
Words count
Description
Unit
Data type
Function
Profil
9472
0x2500
1
Sensor status
0 : Disabled
1 : Enabled
-
U16
READ
4
9473
0x2501
2
Date of last instance
s
DATETIME
READ
4
9475
0x2503
1
Average temperature
°C 10
-2
S16
READ
4
Probe 2:
Dec address
Hex address
Words count
Description
Unit
Data type
Function
Profil
9536
0x2540
1
Sensor status
0 : Disabled
1 : Enabled
-
U16
READ
4
9537
0x2541
2
Date of last instance
s
DATETIME
READ
4
9539
0x2543
1
Average temperature
°C 10
-2
S16
READ
4
Probe 3:
Dec address
Hex address
Words count
Description
Unit
Data type
Function
Profil
9600
0x2580
1
Sensor status
0 : Disabled
1 : Enabled
-
U16
READ
4
9601
0x2581
2
Date of last instance
s
DATETIME
READ
4
9603
0x2583
1
Average temperature
°C 10
-2
S16
READ
4
Multi-utility pulse metering
The following Modbus table can be used only if one of the following profiles is selected:
•
Profile 1 (Single-load Energies)
•
Profile 2 (Multi-load Energies Consumption)
•
Profile 3 (Multi-load Energies Production)
Dec address
Hex address
Words count
Description
Unit
Data type
Function
Profil
12288
0x3000
1
Sensor status
0 : Disabled
1 : Enabled
-
U16
READ
1/2/3
12289
0x3001
2
Date of last instance
s
DATETIME
READ
1/2/3
12291
0x3003
4
Total
-
S64
1/2/3