55
EN
DIRIS B-10L - 551174A - SOCOMEC
Load curves – Load 2
The following Modbus table can be used only if one of the following profiles is selected:
•
Profile 7 (Multi-load Load curves)
Dec address Hex address
Words
count
Description
Unit
Data type
Function
Profil
16448
0x4040
1
Load status
0: Disabled
1: Enabled
-
U16
READ
6/7
16449
0x4041
2
Date (last point)
s
DATETIME
READ
6/7
16451
0x4043
2
Total Positive Active Power - last point
W
U32
READ
6/7
16453
0x4045
2
Total Negative Active Power - last point
W
U32
READ
6
16455
0x4047
2
Total Positive Reactive Power - last point
var
U32
READ
6
16457
0x4049
2
Total Negative Reactive Power - last point
var
U32
READ
6
16459
0x404B
1
Flag - last point
0 : Complete period - date configured
1 : Incomplete period - date not configured
2 : Complete period - date configured
3 : Incomplete period - date not configured
-
U16
READ
6/7
16460
0x404C
2
Date (previous point)
s
DATETIME
READ
6/7
16462
0x404E
2
Total Positive Active Power - previous point
W
U32
READ
6/7
16464
0x4050
2
Total Negative Active Power - previous point
W
U32
READ
6
16466
0x4052
2
Total Positive Reactive Power - previous point
var
U32
READ
6
16468
0x4054
2
Total Negative Reactive Power - previous point
var
U32
READ
6
16470
0x4056
1
Flag - previous point
0 : Complete period - date configured
1 : Incomplete period - date not configured
2 : Complete period - date configured
3 : Incomplete period - date not configured
-
U16
READ
6/7