57
EN
DIRIS B-10L - 551174A - SOCOMEC
Load curves – Load 4
The following Modbus table can be used only if one of the following profiles is selected:
•
Profile 7 (Multi-load Load curves)
Dec address
Hex address
Words
count
Description
Unit
Data type
Function
Profil
16576
0x40C0
1
Load status
0: Disabled
1: Enabled
-
U16
READ
6/7
16577
0x40C1
2
Date (last point)
s
DATETIME
READ
6/7
16579
0x40C3
2
Total Positive Active Power - last point
W
U32
READ
6/7
16581
0x40C5
2
Total Negative Active Power - last point
W
U32
READ
6
16583
0x40C7
2
Total Positive Reactive Power - last point
var
U32
READ
6
16585
0x40C9
2
Total Negative Reactive Power - last point
var
U32
READ
6
16587
0x40CB
1
Flag - last point
0 : Complete period - date configured
1 : Incomplete period - date not configured
2 : Complete period - date configured
3 : Incomplete period - date not configured
-
U16
READ
6/7
16588
0x40CC
2
Date (previous point)
s
DATETIME
READ
6/7
16590
0x40CE
2
Total Positive Active Power - previous point
W
U32
READ
6/7
16592
0x40D0
2
Total Negative Active Power - previous point
W
U32
READ
6
16594
0x40D2
2
Total Positive Reactive Power - previous point
var
U32
READ
6
16596
0x40D4
2
Total Negative Reactive Power - previous point
var
U32
READ
6
16598
0x40D6
1
Flag - previous point
0 : Complete period - date configured
1 : Incomplete period - date not configured
2 : Complete period - date configured
3 : Incomplete period - date not configured
-
U16
READ
6/7