19
EN
DIRIS B-10L - 551174A - SOCOMEC
4.4.3.
TF flexible current sensors
The TF flexible current sensors use the Rogowski principle, covering a wide current range without saturation.
Their flexible design and easy opening system enables a quick installation inside electrical panels, making them particularly
well suited for adding measuring points in existing electrical installations, especially when space is limited.
The secure lock technology prevents non voluntary openings of the Rogowski rope. Thanks to the specific link, they are
recognised by the DIRIS B-10L and a high level of overall accuracy for the measurement chain is guaranteed.
4.4.3.1. Range
Six models are available, covering a large current range up to 6000 A with openings of different shapes and sizes. They
include a compact and self-supplied integrator, required to shape the current signal.
TF-40
TF-80
TF-120
TF-200
TF-300
TF-600
Ø (mm)
40
80
120
200
300
600
I nom. (a.c.)
100 … 400A
150 … 600A
400 … 2000A 600 … 4000A 1600 … 6000A 1600 … 6000A
Part number
4829 0573
4829 0574
4829 0575
4829 0576
4829 0577
4829 0578
4.4.3.2. Dimensions
Dimensions
in
/mm
TF-40
TF-80
TF-120
TF-200
TF-300
TF-600
Diameter D
1.57
40
3.15
80
4.72
120
7.87
200
11.81
300
23.62
600
Perimeter L
4.96
126
9.88
251
14.84
377
24.72
628
37.09
942
74.21
1885
Diameter X
0.28
7
0.33
8.4
Integrator
8.04 x 0.75 x 0.6
128 x 19 x 15
L
D
39.4
39.4
X
1000
1000