33
EN
DIRIS B-10L - 551174A - SOCOMEC
6. CONNECTION
6.1. DIRIS B-10L connection
Optional modules
- Digital In/Out: DIRIS O-iod
- Temperature In: DIRIS O-it
Voltage inputs
50-300VAC (Ph/N)
87-520VAC (Ph/Ph)
Display
DIRIS D-30
Auxiliary supply
110-230VAC
USB
Micro USB type B
10 mm
solid 0.2 mm
2
-> 2.5 mm
2
stranded with ferrule
0.25 mm
2
-> 1.5 mm
2
2x 2 positions - spring-cage
10 mm
solid 0.2 mm
2
-> 2.5 mm
2
stranded with ferrule
0.25 mm
2
-> 1.5 mm
2
2x 6 positions - spring-cage
Current sensor inputs
Recommendation: Use Socomec
Display cable type RJ9 straight,
twisted pairs, non-shielded,
300V cat.III. rated, -20 / +70 °C.
4x current sensor inputs
2 digital inputs
7 mm
solid 0.14 mm
2
-> 1.5 mm
2
stranded 0.14 mm
2
-> 1.5 mm
2
4 positions - screw 0.25 Nm max.
(*) Do not forget to connect earth to the DIRIS B-10L.
(*)