10. 7. U
Ps
s
tatUs
: a
ddrEss
0
x
0140, 3 w
ords
code
description
Bit
address
Remarks
S000
Load supplied by inverter
0
0x0140
S001
Load on automatic bypass
1
S002
Load on maintenance. Bypass
2
S003
Load not supplied
3
S004
Eco-mode
4
S005
Energy Saver
5
S006
UPS in normal mode
6
S007
UPS Starting procedure in progress
7
S008
UPS on maintenance bypass proc. in progress
8
S009
9
S010
10
S011
11
S012
UPS Bypass input supply absence
12
Synthesis of all
units
S013
UPS Rectifier input supply absence
13
S014
14
S015
Remote control enabled
15
S016
Module 1 operating
0
0x0141
S017
Module 2 operating
1
S018
Module 3 operating
2
S019
Module 4 operating
3
S020
Module 5 operating
4
S021
Module 6 operating
5
S022
Module 7 operating
6
S023
Module 8 operating
7
S024
8
S025
9
S026
10
S027
11
S028
12
S029
13
S030
Bypass working
14
S031
15
S032
Module 1 available
0
0x0142
S033
Module 2 available
1
S034
Module 3 available
2
S035
Module 4 available
3
S036
Module 5 available
4
S037
Module 6 available
5
S038
Module 7 available
6
S039
Module 8 available
7
S046
Bypass available
14
m
odbUs
In
Parallel
system
wIth
centralIsed
byPass
29
Delphys green power
- Ref.: IOMDGPJB0910-GB_11
ENGLISH
Содержание DELPHYS BC
Страница 47: ......