10. 8. U
Ps
a
Larms
: a
ddrEss
0
x
0148, 2 w
ords
code
description
Bit
address
Remarks
a000
uPS imminent stop
0
0x0148
a001
UPS overload
1
a002
UPS transfer blocked
2
a003
uPS transfer impossible
3
a004
UPS insufficient Resource
4
a005
UPS Redundancy loss
5
a006
Parallel fault
6
a007
7
a008
8
a009
uPS: Battery alarm
9
synthesis of all unit
alarms
a010
uPS on battery
10
a011
UPS: Battery discharge
11
a012
UPS: End of autonomy
12
a013
uPS: temperature alarm
13
a014
14
a015
15
a016
Module 1 general
0
0x0149
a017
Module 2 general
1
a018
Module 3 general
2
a019
Module 4 general
3
a020
Module 5 general
4
a021
Module 6 general
5
a022
Module 7 general
6
a023
Module 8 general
7
a024
8
a025
9
a026
10
a027
11
a028
12
a029
13
a030
Bypass alarm
14
a031
15
m
odbUs
In
Parallel
system
wIth
centralIsed
byPass
30
Delphys green power
- Ref.: IOMDGPJB0910-GB_11
Содержание DELPHYS BC