The table addresses are written in hexadecimal, beginning with ‘0x’.
Some PLC systems request a relative address starting from 400 (0x0190) or 40001 (0x9C41), on this address it’s
necessary to add the first address of the MODBUS table.
6. 4. f
ramE
Errors
managEmEnt
In case of wrong data request, the DELPHYS Green Power answers with the following frame error :
error function code
error code
cause
80 + code function
1
Function error
80 + code function
2
Addresses error
80 + code function
3
Wrong data
80 + code function
6
busy
80 + code function
8
Write register error
7. conventIonS
11
Delphys green power
- Ref.: IOMDGPJB0910-GB_11
ENGLISH
Содержание DELPHYS BC
Страница 47: ......