8. 7. U
nit
a
Larms
: a
ddrEss
0
x
114a, 4 w
ords
code
description
Bit
address
Remarks
a032
unit imminent stop
0
0x114A
a033
Unit overload
1
a034
Transfer blocked
2
a035
transfer impossible
3
a036
Insufficient Resources
4
only on parallel
a037
5
a038
6
a039
Rectifier critical
7
a040
Inverter critical
8
a041
Bypass critical
9
a042
Common critical
10
a043
Fan alarm
11
a044
Back feed protection open
12
a045
ACS synchro source fault
13
a046
14
a047
15
a048
Operating on battery
0
0x114B
a049
Battery alarm
1
a050
Battery room
2
a051
Battery discharged
3
a052
End of autonomy time
4
a053
Battery test failure
5
a054
Earth leakage fault
6
a055
Battery circuit open
7
a056
on battery with mains oK
8
a057
DC voltage not OK
9
a058
Rectifier preventive
10
a059
inverter preventive
11
a060
Bypass preventive
12
a061
common preventive
13
a062
Mimic panel
14
a063
Ambient T° max
15
a064
0
0x114C
a065
1
a066
2
a067
3
a068
4
a069
5
a070
6
s
Ingle
UnIt
UPs m
odbUs
t
ables
16