10. 2. m
odbUs
tabLE
in
ParaLLEL
sYstEm
witH
cEntraLisEd
bYPass
table
Start addresses table Length In words
modbus function
UPS Identification
0x0100
32
3 read
Date and hours
0x0360
4
3 read
UPS Configurations
0x0120
16
3 read
UPS Status (48 bits)
0x0140
3
3 read
UNIT Status (64 bits)
0xm143
4
3 read
UPS Alarms (32 bits)
0x0148
2
3 read
UNIT Alarm (80 bits)
0xm14A
5
3 read
uPS measurements
0x0200
32
3 read
unit measurements
0xm220
80
3 read
controls permission
0xm150
4
3 read
uPS controls
0xm190
4
6 write
m = 1
- - - - number of module
m = 8
m = 15 Bypass data
Example:
0x3100 = ID of unit 3
0x3140 = UPS States
0xF143 = Bypass 3 states
10. 3. U
Ps
i
dEntification
: a
ddrEss
0
x
0100, 32 w
ords
See unit part
10. 4. d
atE
& H
oUrs
: a
ddrEss
0
x
0360, 4 w
ords
See unit part
10. 5. U
Ps
c
onfigUration
: a
ddrEss
0
xm
120, 16 w
ords
See unit part
10. 6. P
rELiminarY
r
Emarks
Following tables describe only the UPS part (common for all units)
m
odbUs
In
Parallel
system
wIth
centralIsed
byPass
28
Delphys green power
- Ref.: IOMDGPJB0910-GB_11