METERING PRODUCT USE (continued)
The setup menu integrates 6 parame-
ters described in the table hereunder.
The table explains parameters’ definition,
settings possibilities, and default values.
Press
Down push button to access parameter required.
Press
Up push button to come back to previous value, or press
or
Home push button to come back to
SETUP MENU
NOM.VOLT : Phase-Phase
nominal voltage.
From 200 to 480 V
400 V AC
NETWORK : Network configuration.
Type of metering (1P or 3P
phases).
Number of active wires (2L,
3L or 4L)
definition.
1P2L, 1P3L, 3P4L
3P4L
3P3L, 1PAP
NOM.FREQ : Nominal frequency.
50 or 60 Hz
50 Hz
TRANS IHI : Retransfer inhibit feature:
press on RTI button
required to allow retransfer
from gen to main.
Yes or No
No
CNT RST : Reset number of commuta-
tion counter (from Main to
Gen).
Displays no once reset.
Yes or No
No
Definition
Setting range
Default value
Parameter Display
ATI 073 C
CT : winding ratio of current transformers
50/5 to 1600/5
50 / 5 to 1600 / 5
500 / 5