SOCOMEC - Réf.: 678 623 G GB
37
ENGL
ISH
LOAD
Genset controller
201
202
203
204
205
206
101
102
103
104
105
106
1
2
3
N
Power 230 V
ac – – V
o
ltage Sensing
V
o
ltage Sensing – O
O – Power 230 V
a
c
1-2
3-4
5-6
7-8
1-2
3-4
5-6
7-8
A
B
A
B
VOLTAGE CONFIGURATIONS (continued)
ELECTRONIC MODULE CONNECTIONS
The Voltage sensing kit provides power
and sensing to the electronic module
from the generator and the main side.
Main sensing is 3 phases sensing:
103: Neutral
104: Phase 3
105: Phase 2
106: Phase 1
Gen sensing is single phase sensing:
203: Phase 1
205: Phase 3
A. No wiring change required from standard delivery
Configurations:
V502
415 / 240 Vac 50 Hz
V503
400 / 230 Vac 50 Hz
V504
380 / 220 Vac 50 Hz
V603
440 / 254 Vac 60 Hz
V605
380 / 220 Vac 60 Hz
V601
480 / 277 Vac 60 Hz - Special Voltage Option 5 = 277 Vac
3 Phases 4 Wires connections-3P4L
Verify voltage between
101 / 102 & 201 / 202
= 220 / 240 Vac±20 %