SOCOMEC - Réf. : 678 623 G GB
METERING PRODUCT USE (continued)
The functionality is similar to the basic
product (see the “manual mode of the
basic product” paragraph).
The sequence is similar to the basic
product.
MANUAL MODE
This sequence is started as soon as the
unit is in automatic mode and in posi-
tion 2.
Position 2:
• Mains is not available
• Switch is in position 2 (Generator)
• Generator is off
Retransfer Inhibit Feature
• Once the Mains is back, it might be
preferable not to immediately transfer
the load from the generator to the
mains.
• If Retransfer inhibit feature has been
enabled in the programming mode,
the RTI led is on (default value).
• Once retransfer from the Generator
to the Mains is ready, RTI feature
blocks the retransfer and the RTI led
is blinking.
• A manual press on the RTI push but-
ton is necessary to start retransfer.
MAINS RETURN AUTOMATIC SEQUENCE
Specific features
RTI Led
RTI pushbutton
ATI 084 B GB