76
SOCOMEC - Réf. : 678 623 G GB
COMMUNICATION (continued)
Example :
Configuration of 233 V nominal
voltage for ATI n° 5.
Hex
Slave
05
Function
10
High-order
address
02
Low-order
address
06
N° word
00
01
N° octet
02
High-order
word n°
00
Low-order
word n°
E9
CRC 16
76B8
Dec
16
233
ATI reply:
Slave
05
Function
10
High-order
address
02
Low-order
address
06
N° word
00
01
CRC 16
E1F4
89
105
Table of values of the programming zone
Decimal Hexa
Number
Standard
Address
Address of words
Variable
Units
Product
Type of network -
x
0 = 3P4L - 1 = 1P3L
2 = 1P2L - 3 = 3P3L
512
200
1
4 = 1PAP
513
201
1
CT primary
A
x
518
206
1
VNominal
V
x
519
207
1
FNominal - 50 or 60
Hz
x
0 = No, 1 = Yes
521
209
1
Transfer Inhibit Feature
x
522
20A
1
VOver
% (0-100)
x
523
20B
1
VHystOver
% (0-100)
x
524
20C
1
VUnder
% (0-100)
x
525
20D
1
VHystUnder
% (0-100)
x
526
20E
1
VGenOver
% (0-100)
x
527
20F
1
VHystGenOver
% (0-100)
x
528
210
1
VGenUnder
% (0-100)
x
529
211
1
VHystGenUnder
% (0-100)
x
530
212
1
FOver
% (0-100)
x
531
213
1
FHystOver
% (0-100)
x
532
214
1
FUnder
% (0-100)
x
533
215
1
FHystUnder
% (0-100)
x
534
216
1
FGenOver
% (0-100)
x
535
217
1
FHystGenOver
% (0-100)
x
536
218
1
FGenUnder
% (0-100)
x
537
219
1
FHystGenUnder
% (0-100)
x
538
21A
1
1MT Timer
min
x
539
21B
1
2 MT Timer
s
x
540
21C
1
AT Timer
s
x
541
21D
1
DBT Timer
s
x
542
21E
1
ROT Timer
min
x
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3) (continued)
Содержание ATI 1000 A
Страница 1: ...Transfer Panel ATI Technical Instruction Manual...
Страница 85: ...SOCOMEC R f 678 623 G GB 85 ENGLISH...
Страница 86: ...86 SOCOMEC R f 678 623 G GB...