TAKEDO - 3VF NXP USER MANUAL Release P09.1 dated 01-12-2017
27
P2.10.9:
Switching Frequency
(maintain the default value).
2.10.10
Maximum Emergency Speed in “Battery Saving” or “Constant Pressure Push-
button”
It is the speed, expressed in m/sec, that the car shall not exceed during “Battery Saving” or “Constant
Pressure Push-button” operation. It can be adjusted from 0 to the rated speed set in P2.2.2.
If set to 0, the “Constant Pressure Push-button” emergency operation is DISABLED.
P2.10.11
Minimum Emergency Speed
P2.10.12
Minimum Speed Time
It is effective only in “Battery Saving” operation (see above).
P2.10.13.1 Motor Control Mode :
(Frequency, Open Loop, Closed Loop)
If the input supply voltage is lower than 96V, “Frequency” control is the preferred mode in an evacuation
situation; for PM synchronous motors you must always select the “Closed Loop” control.
P2.10.13.2 Current Control Delay
It is the delay of the inverter in reading current and/or torque when choosing the favorable run direction.
P2.10.13.3 Counter-rotation Gain in Emergency Operation
It is expressed in % of the counter-rotation gain in normal operation and 0 is the recommended value.
7 – CHECKS AND MAINTENANCE
To ensure long service life and smooth operation of the drive, carry out the following checks at regular
intervals. Always isolate the drive from the power supply and make certain the keypad is off before
proceeding.
1- Remove the dust that collects on the cooling fans and on the control circuit board, preferably by means
of compressed air or using a vacuum cleaner.
2- Check that there are no screws loose at the power or control terminals.
3- Check that inverter function is <<normal>> and there is no abnormal overheating.
7.1 MEGGER TEST
When performing insulation tests using a Megger tester
on the input/output cables or on the motor, remove all
the connections to all terminals of the drive and perform
the test only on the power circuit, in accordance with
the adjacent diagram.
Do not Megger test the control circuits.
INVERTER
Содержание TAKEDO-3VF
Страница 8: ...TAKEDO 3VF NXP USER MANUAL Release P09 1 dated 01 12 2017 8 INTENTIONALLY BLANK PAGE ...
Страница 28: ...TAKEDO 3VF NXP USER MANUAL Release P09 1 dated 01 12 2017 28 ASYNCHRONOUS MOTORS CLOSED LOOP ...
Страница 35: ...TAKEDO 3VF NXP USER MANUAL Release P09 1 dated 01 12 2017 35 PERMANENT MAGNET SYNCHRONOUS MOTORS ...
Страница 50: ...TAKEDO 3VF NXP USER MANUAL Release P09 1 dated 01 12 2017 50 ...
Страница 52: ...TAKEDO 3VF NXP Attachment for A3 Amendment Version 03 1 dated 01 12 17 2 PAGE BLANK WITH PURPOSE ...
Страница 58: ...TAKEDO 3VF NXP Attachment for A3 Amendment Version 03 1 dated 01 12 17 8 ...
Страница 59: ...TAKEDO 3VF NXP Attachment for A3 Amendment Version 03 1 dated 01 12 17 9 ...