-28-
NO.ZK2-OM00501-B
<Operation>
Press the
or
button in function selection mode to display [F 2].
Press the
button to set.
Move on to setting of pressure.
Setting ON point of the supply pilot valve
Press the
button to set.
Move on to the next parameter.
Setting OFF point of the supply pilot valve
Press the
button to set.
Move on to the next parameter.
Set the range in which ON point of the supply pilot valve input is prohibited
Press the
button to set.
Return to function selection mode.
[F 2] Setting of OUT2 complete.
1: Selected parameter become effective after pressing the
button.
2: After setting is made valid by the
button, it is possible to move to measurement mode by pressing the
button for 2 seconds or
longer.
3: OFF point (H_2) of the supply pilot valve is automatically corrected by setting the input prohibited range (H_4) of ON point of the
supply pilot valve.
Press the
or
button to change the set points.
A