-31-
NO.ZK2-OM00501-B
Auto-preset
When auto-preset is selected in function selection mode, the set value can be calculated and memorized
from the measured pressure. Repeating the suction and release of a workpiece several times automatically
optimizes the set value.
1, Selection of auto-preset OUT1
Press the
button in measurement mode to display "AP1".
2, Preparation of equipment for OUT1
Prepare equipment for which the pressure of OUT1 is to be set.
3, Setting of auto-preset for OUT1
Press the
button, the display will show
“A1L" and pressure measurement
begins.
Operate the equipment and change the pressure
.
When the a pressure change is detected, [A1H] will be displayed automatically,
continue operating the equipment in the same manner for several cycles.
4, Completion of setting
Press the
button to set [P_1] and [H_1] (in reverse output mode [n_1] and [H_1] are set) and complete
auto-preset mode. The pressure switch will then return to measurement mode.
([n_1] and [H_1] are set in reverse output mode.)
The settings made in auto-preset mode are as follows.
P_1 = A-(A-B)/4
A = Maximum pressure value
H_1 = | (A-B)/2|
B = Minimum pressure value
To clear the stored auto-preset settings, press the
and
buttons simultaneously for 1 second or
longer.
Содержание ZK2-ZSV-A Series
Страница 22: ...21 NO ZK2 OM00501 B Reversed output out1 A...