5 Adjustments
5-25
Click
OK
to return to the S
-V component Main window. If Pn103 (Moment of
Inertia (Mass) Ratio) has been changed, that new value will remain.
-
Autotuning without Reference Input
To execute autotuning without using a reference input, use the following procedure.
1. Select the
No reference input
option under
Reference input from host controller
in the
Tuning main window, and then click
Autotuning
. The Autotuning-Setting Conditions
box will appear.
2. Select whether or not to use the load moment of inertia (load mass) identification
from the
Switching the load moment of inertia (load mass) identification
box, the mode
from the
Mode selection
box, the mechanism from the
Mechanism selection
box, and
enter the moving distance. Then, click
Next
.
•
Calculating Moment of Inertia
Select the mode to be used. Usually, set to the Moment of inertia calculated.
Содержание LECYU Series