12.2
Alarm Content
・
Countermeasure
Group
The
condition of
the
controller
when an
alarm is
generated
How to
clear
the
alarm
Condition / Countermeasure
<Condition>
Problem occurred with the controller data or parameters.
B
Any
condition
Input
RESET
<Countermeasure>
If the problem is not solved by supplying power again, contact SMC.
<Condition>
During the pushing operation, the actuator is pushed back beyond the
start position of pushing.
C
During or
after
pushing
operation
Input
RESET
<Countermeasure>
Set a larger pushing thrust or reduce the reaction force of the load.
Refer to
for details of pushing
operation.
<Condition>
This is generated when return to origin, positioning, pushing or a jog
operation is commanded when the servo is OFF.
C
Stopped
Input
RESET
<Countermeasure>
Check if I/O signal STOP is input. Also, check if the servo is OFF in
manual mode. Refer to
8.5 Servo ON (P.43)
for turning off the servo.
<Condition>
This is generated when positioning, pushing is commanded before
return to origin is completed.
C
Stopped
Inpu
t
RESET
<Countermeasure>
Start operation after the completion of the return to origin. Return to
origin must be performed after a group D alarm is generated and
deactivated.
<Condition>
Motor rotation exceeds specified value.
D
During
operation
Input
RESET
<Countermeasure>
If an external force is being applied, remove it. If there is no external
force being applied, and the problem is not solved by supplying power
again, please contact SMC.