Troubleshooting list
Problem
No.
Problem
Problem possible
causes
Investigation method
Countermeasures
1
•
Output remains
ON.
Indicator LED
remains ON.
•
Output remains
OFF.
Indicator LED
remains OFF.
Incorrect
pressure setting
(1) Check the set pressure.
(2) Check the operation mode,
hysteresis and output type.
(hysteresis mode/window
comparator mode,
normal/reversed output)
(1) Reset the pressure
setting.
(2) Reset the function
settings.
Product failure
Replace the product.
2
Output remains
ON.
Indicator LED
works correctly.
Incorrect wiring
Check the wiring of the output.
Check if the load is connected
directly to DC(+) or DC(-).
Correct the wiring.
Product failure
Replace the product.
3
Output remains
OFF.
Indicator LED
works correctly.
Incorrect wiring
Check the wiring of the output.
Check if the load is connected
directly to DC(+) or DC(-).
Correct the wiring.
Unsuitable model
selection
Check the SW output specification
setting.
Check if the SW output is PNP while
NPN is intended to be set, and vice
versa.
Set the SW output
specification again.
Broken lead wire
Check if there is bending stress
applied to any parts of the lead wire.
(bending radius and tensile force
applied)
Correct the wiring
conditions. (adjust the
tensile force and increase
the bending radius.)
Product failure
Replace the product.
4
Switch output
generates
chattering.
Incorrect wiring
Check the wiring.
Check if the brown and blue wires are
connected to DC(+) and DC(-)
respectively, and if the output wiring
is loose (contact failure).
Correct the wiring.
Incorrect settings
(1) Check the set pressure.
(2) Check that the hysteresis range is
not too narrow.
(3) Check the delay time setting.
Check if the delay time is too
short.
(1) Reset the pressure
setting.
(2) Increase the hysteresis.
(3) Reset the function
settings.
Product failure
Replace the product.
5
Slow switch
output response
Incorrect
pressure setting
Check the pressure setting.
Check that the detected pressure and
the set pressure value are not the
same or not too close.
Reset the pressure setting.
Set the pressure setting
value so it is not too close to
the detected pressure.
Содержание ISE20CH-L
Страница 96: ...95 No PS OMX0002 Dimensions 02 type...
Страница 97: ...96 No PS OMX0002 F02 type C01 type A2 type B2 type...
Страница 98: ...97 No PS OMX0002 02L type...
Страница 99: ...98 No PS OMX0002 F02L type C01L type A2L type B2L type...
Страница 100: ...99 No PS OMX0002 Bracket mounting dimensions Bracket A...
Страница 101: ...100 No PS OMX0002 Bracket C...
Страница 103: ...102 No PS OMX0002 Mounting dimensions of panel mount adapter bottom piping type...
Страница 104: ...103 No PS OMX0002 Mounting dimension of panel mount adapter bottom piping type Front protective cover...
Страница 106: ...105 No PS OMX0002 Vertical...