-65-
No.PS
※※
-OMX0002
■
Process data
Process data is the data which is exchanged periodically between the master and device.
This product process data consists of switch output status, error diagnostics and pressure gauge
measurement value.
(Refer to the table below.)
Bit offset
Item
Notes
0
OUT1 output
0: OFF 1: ON
1
OUT2 output
0: OFF 1: ON
2
Diagnosis
0: Normal 1: Abnormal
Set with the index 0x03EB.
∗
: Refer to the table (diagnostic information).
3 to 15
Pressure gauge
measurement value
Unsigned 13bit
∗
: Refer to the table (Unit specification and pressure gauge measurement value (PD)).
Bit offset
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Item
Pressure gauge measurement value (PD)
Diagnosis
OUT2
OUT1
•The process data of this product is Big-Endian type.
When the transmission method of the upper communication is Little-Endian, the byte order will be changed.
Refer to the table below for the Endian type of the major upper communication.
Endian type
Upper communication protocol
Big-Endian type
Such as PROFIBUS and PROFINET
Little-Endian type
Such as EtherNET/IP, EtherCAT and CC-Link IE Field.
○
Diagnostic information
This product can detect the device error by diagnostic bit in the process data.
Monitoring items of the device condition can be set by the diagnostic information selection [F_0].
Set value
Content
ALL
All errors
Diagnostic bit will be "1: ON" when either of the following errors is generated.
•Product internal failure
•Residual pressure error
•Exceeding upper limit of the temperature in the product
•Out of the rated pressure (when HHH and LLL are generated.)
PrES
Pressurizing error
Diagnostic bit will be "1: ON" when the following error is generated.
•Out of the rated pressure (when HHH and LLL are generated.)
oFF
Unused
Disgnostic information is not used.
Содержание ISE20CH-L
Страница 96: ...95 No PS OMX0002 Dimensions 02 type...
Страница 97: ...96 No PS OMX0002 F02 type C01 type A2 type B2 type...
Страница 98: ...97 No PS OMX0002 02L type...
Страница 99: ...98 No PS OMX0002 F02L type C01L type A2L type B2L type...
Страница 100: ...99 No PS OMX0002 Bracket mounting dimensions Bracket A...
Страница 101: ...100 No PS OMX0002 Bracket C...
Страница 103: ...102 No PS OMX0002 Mounting dimensions of panel mount adapter bottom piping type...
Страница 104: ...103 No PS OMX0002 Mounting dimension of panel mount adapter bottom piping type Front protective cover...
Страница 106: ...105 No PS OMX0002 Vertical...