-31-
No.PS
※※
-OMX0002
●
[F 1] Setting of OUT1
Page
Item
Explanation
Default setting
Output mode
Either hysteresis mode, window comparator mode, error output or
output off can be selected.
Hysteresis mode
Reversed output
Selects which type of switch output is used, normal or reversed.
Normal output
Pressure setting
Sets the ON and OFF point of the switch output.
ISE20C
: 0.500 MPa
ZSE20C
: -50.5 kPa
ZSE20CF : 50.0 kPa
ISE20CH : 1.000 MPa
Hysteresis
Appropriate setting of the hysteresis will prevent the switch output
from chattering.
ISE20C
: 0.050 MPa
ZSE20C
: 5.1 kPa
ZSE20CF : 5.0 kPa
ISE20CH : 0.100 MPa
Delay time
Delay time of the switch output can be selected.
0.00 sec
Display color
Selects the output according to the display color.
OUT1 ON : Green
OUT1 OFF: Red
●
[F 2] Setting of OUT2
Page
Same setting as [F 1] OUT1.
●
Other parameter settings
Item
Page
Default setting
[F 3] Digital filter setting
Page
0.00 s
[F 4] Auto-preset function
Page
Not used
[F 6] Fine adjustment of display value
Page
0%
[F10] Sub display setting
Page
std (Standard)
[F11] Display resolution setting
Page
1000-split
[F14] Zero cut-off setting
Page
0.0
[F80] Power saving mode
Page
OFF
[F81] Security code
Page
OFF
[F90] Setting of all functions
Page
OFF
[F96] Number of pressurizing errors
Page
-
[F98] Output check
Page
N/A (normal output)
[F99] Reset to default settings
Page
OFF
Содержание ISE20CH-L
Страница 96: ...95 No PS OMX0002 Dimensions 02 type...
Страница 97: ...96 No PS OMX0002 F02 type C01 type A2 type B2 type...
Страница 98: ...97 No PS OMX0002 02L type...
Страница 99: ...98 No PS OMX0002 F02L type C01L type A2L type B2L type...
Страница 100: ...99 No PS OMX0002 Bracket mounting dimensions Bracket A...
Страница 101: ...100 No PS OMX0002 Bracket C...
Страница 103: ...102 No PS OMX0002 Mounting dimensions of panel mount adapter bottom piping type...
Страница 104: ...103 No PS OMX0002 Mounting dimension of panel mount adapter bottom piping type Front protective cover...
Страница 106: ...105 No PS OMX0002 Vertical...