-70-
No.PS
※※
-OMX0002
●
Device access lock parameters (index 12)
The contents are as follows.
Data type: 16 bit Record
Value (dec)
Contents
0x0000(0)
Key lock release, DS unlock (Initial value)
0x0002(2)
Key lock release, DS lock
0x0008(8)
Key lock, DS unlock
0x000A(10)
Key lock, DS lock
[Key lock]
This function prevents the user from physically changing the setting of the pressure switch (button
operation is not accepted).
Even when key lock function is activated, settings can be changed by IO-Link communication.
Restoration by data storage (overwriting parameter data) can be performed.
[Lock data storage (DS lock)]
Locking "Data storage" will invalidate the data storage function of the pressure switch.
In this case, access will be denied for backup and restoration of data storage.
●
Device state parameters (index 36)
Readable device states are as follows.
Data type: 8 bit UInteger
Value (dec)
State definition
Description
0x00(0)
Normal operation
-
0x01(1)
Maintenance inspection required
Not available
0x02(2)
Outside specification range
Device temperature upper limit exceeded
Measured pressure range upper limit exceeded
Falls below measured pressure range lower limit
0x03(3)
Function check
Not available
0x04(4)
Failure
Internal failure of digital pressure switch
●
Device detail status parameters (index 37)
Detailed event contents of readable device status are as follows.
Array
Event content
Event classification
Event code
Definition
Value
1
Internal failure of digital pressure switch
Error
0xF4
0x8D01
2
Internal failure of digital pressure switch
Error
0xF4
0x8D02
3
Internal failure of digital pressure switch
Error
0xF4
0x8D03
4
Internal failure of digital pressure switch
Error
0xF4
0x8D04
5
Internal failure of digital pressure switch
Error
0xF4
0x8D05
6
Internal failure of digital pressure switch
Error
0xF4
0x8D06
7
Internal failure of digital pressure switch
Error
0xF4
0x8D07
8
-
-
0x00
0x0000
9
Device temperature upper limit exceeded
warning
0xE4
0x4210
10
Measured pressure range upper limit exceeded
warning
0xE4
0x8C10
11
Fell below measured pressure range lower limit
warning
0xE4
0x8C30
12
-
-
0x00
0x0000
13
-
-
0x00
0x0000
14
Data storage upload request
notification
0x54
0xFF91
Содержание ISE20CH-L
Страница 96: ...95 No PS OMX0002 Dimensions 02 type...
Страница 97: ...96 No PS OMX0002 F02 type C01 type A2 type B2 type...
Страница 98: ...97 No PS OMX0002 02L type...
Страница 99: ...98 No PS OMX0002 F02L type C01L type A2L type B2L type...
Страница 100: ...99 No PS OMX0002 Bracket mounting dimensions Bracket A...
Страница 101: ...100 No PS OMX0002 Bracket C...
Страница 103: ...102 No PS OMX0002 Mounting dimensions of panel mount adapter bottom piping type...
Страница 104: ...103 No PS OMX0002 Mounting dimension of panel mount adapter bottom piping type Front protective cover...
Страница 106: ...105 No PS OMX0002 Vertical...