4
How to use
-98-
No.PS
※※
-OMW0009-A
●
Device access lock parameter (index 12)
The contents are as follows.
Data type: 16 bit Record
Value
Contents
0
Key lock release, DS unlock (Initial value)
2
Key lock release, DS lock
8
Key lock, DS unlock
10
Key lock, DS lock
[Key lock]
This function prevents the user from physically changing the setting of the pressure switch (button
operation is not accepted).
Even when key lock function is activated, settings can be changed by IO-Link communication.
Restoration by data storage (overwriting parameter data) can be performed.
[Lock data storage (DS lock)]
Locking "Data storage" will invalidate the data storage function of the pressure switch.
In this case, access will be denied for backup and restoration of data storage.
●
Device state parameters (index 36)
Readable device states are as follows.
Data type: 8 bit UInteger
Value
State definition
Description
0
Normal operation
-
1
Maintenance inspection required
Not available
2
Outside specification range
Less than the lower limit of the pressure measurement range
3
Function check
Not available
4
Failure
Internal failure of digital pressure switch
●
Device detail status parameters (index 37)
Detailed event contents of readable device status are as follows.
Array
Event content
Event classification
Event code
Definition
Value
1
Internal failure of digital pressure switch
Error
0xF4
0x8D01
2
Internal failure of digital pressure switch
Error
0xF4
0x8D07
3
Internal failure of digital pressure switch
Error
0xF4
0x8D02
4
Internal failure of digital pressure switch
Error
0xF4
0x8D03
5
Internal failure of digital pressure switch
Error
0xF4
0x8D04
6
Internal failure of digital pressure switch
Error
0xF4
0x8D05
7
Internal failure of digital pressure switch
Error
0xF4
0x8D06
8
Pressure sensor error
Error
0xF4
0x8CD0
9
Short circuit of OUT2 output terminal
Error
0xF4
0x8CC0
10
Temperature sensor error
Error
0xF4
0x8CD1
11
Below the SUP port minimum pressure range
warning
0xE4
0x8D71
12
Below the OUT port minimum pressure range
warning
0xE4
0x8D72
13
Test event A
warning
0xE4
0x8CA0
14
Test event B
warning
0xE4
0x8CA1
15
Data storage upload request
notification
0x54
0xFF91
Содержание ISA3-F series
Страница 1: ...No PS OMW0009 A PRODUCT NAME Digital Gap Checker compatible MODEL Series Product Number ISA3 series ...
Страница 10: ...2 About this product 9 No PS OMW0009 A With control unit ...
Страница 23: ...2 About this product 22 No PS OMW0009 A ISA3 Without control unit DIN rail mounting ...
Страница 24: ...2 About this product 23 No PS OMW0009 A ISA3 B L1 3 5 7 With control unit Bracket mounting ...
Страница 25: ...2 About this product 24 No PS OMW0009 A ISA3 B R1 3 5 7 ISA3 B R0 2 4 6 8 ISA3 B LN ISA3 B RN ...
Страница 42: ...3 Installation 41 No PS OMW0009 A Part structure Without control unit ...
Страница 43: ...3 Installation 42 No PS OMW0009 A With control unit Supply port Left side ...
Страница 44: ...3 Installation 43 No PS OMW0009 A With control unit Supply port Right side ...
Страница 115: ...5 Troubleshooting 114 No PS OMW0009 A Relationship between supply pressure and display ...