Installation
-30-
No.PS
※※
-OMW0009-A
○Restrictor setting of 2 port solenoid valve
Air can be continuously supplied by adjusting the restrictor. This reduces the possibility of water or cutting
oil etc. entering the 2 port solenoid valve from the OUT port (detection port).
Turn off the power to the 2 port solenoid valve.
Adjust the restrictor by turning the screw with a flat head screw driver etc.
Clockwise: Restrictor closed
Counterclockwise: Restrictor opened
: Do not turn the restrictor screw more than 5 rotations
from the fully closed position as the screw will come out.
Turn on the 2 port solenoid valve. Check that no water or cutting oil etc. is exhausted from the detection
nozzle.
When water or cutting oil etc. is exhausted, turn the restrictor screw in a clockwise direction (closing).
Содержание ISA3-F series
Страница 1: ...No PS OMW0009 A PRODUCT NAME Digital Gap Checker compatible MODEL Series Product Number ISA3 series ...
Страница 10: ...2 About this product 9 No PS OMW0009 A With control unit ...
Страница 23: ...2 About this product 22 No PS OMW0009 A ISA3 Without control unit DIN rail mounting ...
Страница 24: ...2 About this product 23 No PS OMW0009 A ISA3 B L1 3 5 7 With control unit Bracket mounting ...
Страница 25: ...2 About this product 24 No PS OMW0009 A ISA3 B R1 3 5 7 ISA3 B R0 2 4 6 8 ISA3 B LN ISA3 B RN ...
Страница 42: ...3 Installation 41 No PS OMW0009 A Part structure Without control unit ...
Страница 43: ...3 Installation 42 No PS OMW0009 A With control unit Supply port Left side ...
Страница 44: ...3 Installation 43 No PS OMW0009 A With control unit Supply port Right side ...
Страница 115: ...5 Troubleshooting 114 No PS OMW0009 A Relationship between supply pressure and display ...